A variable frequency drive is an electronic device that allows you to start, stop, and control the speed of a three phase motor. It is also a motor starter as it is equipped with overload protection. Read more »
What is the difference between a 'new surplus' motor and a 'factory new' motor?
Our New Surplus electric motors and drives are new and unused overstock or discontinued items offered at lower prices and come with our 90-day warranty.
Factory New products are competitively priced and come with a manufacturers warranty.
Variable frequency drives (VFDs or inverters) now play an important part in major industry.
Within the last 10 years they have been perfected to control and vary the speed of 3 phase electric motors. They serve many purposes, besides speed control. Homeowners and hobbyist alike, who have lathes or milling machines with a 3 phase motor, usually don't have 3 phase power to operate. These VFDs (instead of using a rotary phase converter) can now be used to convert single phase power to 3 phase power. Read more »
FRENIC-Eco drives offer simple installation, quick start-up, easy maintenance, and functionality targeted specifically for variable torque fans and pumps. With functions like: PID with sleep mode, enhanced energy savings, low torque detection, overload avoidance, loss of speed reference control, cascade pump control, and communication protocols for both commercial and industrial facilities: the FRENIC-Eco series of drives are ideally suited for almost any variable torque application
Model #: ECO F1
Input Voltage: 200-230 Volts; 3-Phase
Output Voltage: 0-230 Volts; 3-Phase
Constant Torque HP: --
Constant Torque Amps: --
Variable Torque Horsepower: 125
Variable Torque Amps: 343
Enclosure: IP20
NEMA 1 kit part number: NEMA1-110F1-2
Dimensions (HxWxD): 34.6" x 26.8" x 15.6"
Factory New with manufacturer's warranty
Can be used with single phase input for 125 HP 3 phase motor (114 amps)
Note: Includes separately mounted and wired open DC Link Reactor
Can be used with single phase input for 1 HP 3 phase motor (2.4 amps)
Note: Includes separately mounted and wired open DC Link Reactor
Enclosure: UL Open Type (IP20/IP00) Optional UL Type 1
Ambient Temperature: +14 °F to +122 °F (-10 °C to +50 °C) - UL Open Type / +14 °F to +104 °F (-10 °C to +40 °C) - UL Type 1
Storage Temperature: -13 °F to +149 °F (-25 °C to +65 ° C)
Humidity: 5% to 95% With No Condensation
Altitude: 0 to 3300 ft. (1000 m) Without Derating Derate Output Current for Higher Altitudes per User's Manual
Codes and Standards: UL508C C22.2 No.14 EN61800-5-1:2007
Input Voltage: Tolerance Unbalance: 3-Ph Input = +10% to -15%
Input Frequency: Nominal Tolerance: 50/60Hz +/-5%
Displacement Power Factor: >0.98 (@ Rated Load)
Maximum Output Frequency: 120Hz
Motor Control Method: V/f
Overload Capacity: 120% Rated Current for 1 min.
Analog Inputs: Qty 2: 0 to +10VDC
Analog Inputs: Qty 1: 4 to 20mA
Digital Inputs: Qty 7: Programmable Inputs
Analog Outputs: Qty 1: Configurable for 0 to +10VDC or 4 to 20mA User Selectablefor Proportional Analog Signal Functionality
Analog Outputs: Qty 1: 4 to 20mA User Selectable for Proportional Analog Signal Functionality
Digital Outputs: Qty 1: Form C (1N.O. & 1N.C.) Dry Contacts Rated 0.3A @ 230VAC Max w/ User Selectable Functionality
Digital Outputs: Qty 1: Form A (1N.O.) Dry Contact Rated 0.3A @ 230VAC Max User
Digital Outputs: Qty 3: Transistor Output Rated 50mA @ 27Vdc Max User